![]() When it comes down to sizing your generator engine SCI recommends consulting a licensed electrician to inspect your building or facility demands. An electrician or electrical engineer should be the individuals calculating the requirements. Scherbon can provide you with a qualified electrician or engineer to assist you in this process if need be. know your requirements by making a list of items that you will need to be backed in case of an emergency. each item on your list has an electrical load that you can add up to determined the size unit you will need. With these charts below you can properly size your generator unit to your electrical load. Click Here for a Three phase chart | Click Here for a Single phase chart These formulas will help you calculate the amps to size your needed switch gear and wire size. For three phase: Take the KW x 1000, then divide 1.732, and then divide that number by .80 this = AMPS For single phase: Take the KW x 1000, then divide 1.732 this =AMPS ![]() SCI is a proud member of the EGSA |